Houston Home Inspection, Home Inspector, House Inspection, House Inspector.                                       

         HOME

              

WHY               

Why do I need a home inspection?

 

BUYER/SELLER

Whether you are buying or selling a house, here's some good information for you.

 

     

 

   TREC GUIDELINES  

Texas Real Estate Commission's minimum guidelines all Texas inspectors must follow.

 

     SAFETY                  

Our primary focus on every inspection.  Is the house safe to live in?  Here's some tips.

 

          LINKS

Additional information for the home buyer.

 

 

INDEX

STRUCTURAL

bulletFOUNDATIONS
bulletROOF COVERING
bulletROOF STRUCTURE
bulletWALLS
bulletCEILINGS/FLOORS
bulletDOORS
bulletWINDOWS
bulletFIREPLACE
bulletPORCH, DECK

MECHANICAL

bulletELECTRICAL
bulletHEATING
bulletCOOLING
bulletDUCTS, VENTS
bulletPLUMBING
bulletDRAINS, VENTS
bulletWATER HEATER
bulletAPPLIANCES

OPTIONAL REPORTS OFFERED

bulletLAWN SPRINKLERS
bulletPOOLS, SPA
bulletPRIVATE WELL
bulletPRIVATE SEWER

 

INSPECTOR SELECTION TIPS:

bullet

License No.

bullet

Reports

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TREC GUIDELINES

 

LONE STAR HOME INSPECTIONS provides to you a thorough inspection and a professionally printed report.  Hundreds of items are inspected at every home inspection.  To give you a better understanding of what to expect we have included this section to provide to you the Texas Real Estate Commission's Standards of Practice.  These guidelines regulate the inspection process in Texas.  Every home inspection incorporates these standards at a minimum.  Before buying a home we recommend you review the Standards of Practice. 

 

Standards of Practice

Texas Real Estate Commission Rules Relating to the Provisions of The Real Estate License Act

Adopted Rules 

R. Licensed Real Estate Inspectors

§§535.227-535.231

The Texas Real Estate Commission (TREC) adopts new §§535.227-535.231, concerning standards of practice, with

changes to the proposed text as published in the

December 31, 1999, issue of the Texas Register (24

TexReg 11871). The new sections are adopted in

connection with the repeal of §535.222 of this title (relating to Standards of Practice). These actions divide the current standards of practice for inspectors into five sections to make the standards easier to read and to cite. Generally, the new sections track the content of the current standards of practice, listing the systems, components and items in a home the inspector must include in an inspection unless the inspector’s client agrees to limit the scope of the inspection. The new sections continue to establish the minimum standards for an inspection performed by a licensed inspector. The new sections also contain a number of substantive changes recommended by the Texas Real Estate Inspector Committee, an advisory committee of nine professional inspectors appointed by TREC.

New §535.227 addresses general provisions: definitions,

the scope of an inspection, departure provisions, under

which an inspector may exclude an item from the

inspection, and enforcement. New §535.228 addresses

inspection guidelines for structural system, including the

foundation, walls and doors, windows, fireplace and

chimney, roof, porches and decks. New §535.229

addresses inspection guidelines for mechanical systems:

appliances, cooling systems, heating systems, ducts,

vents and flues, and plumbing systems. New §535.230

addresses inspection guidelines for electrical systems.

New §535.231 addresses optional systems, such as

swimming pools or septic systems, which an inspector

may agree to inspect.

The Texas Association of Realtors (TAR) generally

supported adoption of the new sections but suggested

extensive changes to the proposed text. The Texas Real

Estate Inspector Committee reviewed the suggestions at

public meetings on January 14, 2000, and March 10, 2000,

and recommended their inclusion in the final version of the new sections. The commission concurred with the

committee’s recommendations and modified the final text

to reflect the following changes. Where possible,

definitions were deleted if the ordinary definition of the term is sufficiently clear. The sections were broken into smaller subdivisions to make them easier to read and to cite. In most instances, references to "hazards" were deleted as unnecessary, since most of the conditions an inspector is required to report relate to the health or safety of the occupants of the home. More precise language was used to indicate which items must be inspected and which conditions or deficiencies must be reported or reported as in need of repair by the inspector, rather than implying the need to report the condition or item as in need of repair if the inspector is required to inspect for the presence, or absence, of an item or condition. In most cases, the inspector would be required to report the item or condition under the general scope provision of §535.227; the final version of the text of the new sections merely clarifies for each item or condition whether it is to be reported or reported as in need of repair so as to avoid any confusion on the point.

The Texas Real Estate Inspector Committee also recommended changes based on public comments and

discussion at its meetings. The commission concurred and

made the following changes. More specific language was

added to §535.228 to describe the structural components of guardrails. A requirement for reporting the absence of a

range exhaust vent in §535.229 was broadened to include

electric ranges, since a range exhaust vent serves a fire

protection function for electric ranges as well as gas ranges.

A specific limitation was added to §535.230 to clarify that

the inspector is not responsible for determining whether

circuit breakers are accurately labeled in a service panel.

Language was added to the same section to require the

inspector to use a separate testing device (other than the

built-in GFCI test button) to determine if the GFCI protection device operates properly. A provision relating to parallel wiring in §535.230 was deleted as unnecessary.

Inspections of outbuildings under §535.231 will be subject

to the same standards governing inspection of the principal structure with regard to electrical, plumbing, heating, ventilation or air-conditioning systems. A provision was deleted in §535.231 which appeared to require an inspector to perform a coliform analysis of the well water, when the inspector might not be authorized to do so. A provision was added to §535.231 to require the inspector to report the proximity of septic systems when inspecting a private water well, to be consistent with the requirements when inspecting the septic system. Inspections of swimming pool heaters must be conducted under the same standards as apply generally to a heating system, and a subsection relating to built-in security and fire protection equipment was deleted as in possible conflict with standards governing persons holding another state license to perform such inspections.

The Texas Association of Real Estate Inspectors commented generally in support of the new sections with

the changes recommended by the Texas Real Estate

Inspector Committee.

A number of comments were made by individual inspectors

in opposition to the proposed new sections. One inspector

questioned whether the amount of time required for an inspector to complete a report under the new standards

would create economic pressure on consumers, assuming

any increase in the cost of business by an inspector would

be passed on to the consumer. Based on the recommendation of the Texas Real Estate Inspector

Committee, the commission determined that the changes

in the standards primarily confirmed what should have been included in the inspector’s report under the existing

standards and declined to reduce the information to be

provided to the consumer. Several inspectors questioned

whether the standards should refer to any specific building

code and whether the standards were becoming overly

concerned with enforcement of building codes. Based on

the recommendation of the Texas Real Estate Inspector

Committee, the commission determined that the single

reference to ground fault circuit interruptor devices in a

specific electric code was necessary in the interest of

consumer safety and that reliance upon building codes as

a basis for reporting items in need of repair was appropriate to provide a consistent means of determining when repairs were needed. A number of inspectors suggested replacing terms used in the standards with their more commonly used counterparts, such as replacing "garbage disposer" with "garbage disposal" or replacing "garage door operator" with "garage door opener." Based on the recommendation of the Texas Real Estate Inspector Committee, the commission determined that the language used in the standards was technically correct and declined to make the requested changes.

The new sections are adopted under Texas Civil Statutes,

Article 6573a, §5(h), which authorize the Texas Real Estate Commission to make and enforce all rules and regulations necessary for the performance of its duties.

 

§535.227. Standards of Practice: General Provisions.

(a) Definition of terms. The following words have the

following meanings, unless the context clearly indicates

otherwise.

(1) Act - The Real Estate License Act, Article 6573a, Texas Civil Statutes.

(2) Functioning - Performing in an expected or required manner; carrying out the design purpose or intended operation of a part, system, component, member.

(3) Inaccessible - Not having access without the use

of special tools, equipment, or instruments, or removing

doors, walls, stored items or similar obstructions, or by

causing damage to a structure, finish or component,

equipment or system, or by virtue of inadequate

clearance, walkways, passageways, or hazardous

condition.

(4) In Need of Repair - Does not adequately function

or perform.

(5) Inspect - To look at and examine accessible items, parts, systems or components without, except as required by the rules of the Texas Real Estate Commission, laboratory, scientific or engineering evaluation or testing, destructive tests or the dismantling or removal of parts, members or components. 

(6) Inspector - A person licensed as a professional

inspector, a person licensed as an apprentice inspector or

a person licensed as a real estate inspector.

(7) Performance - The act of carrying out, completing, executing or achievement of an operation, design or function in a manner consistent with the intent of the manufacturer, designer or accepted industry practice.

(8) Report - A written or oral communication of the

inspector’s opinions, observations, determinations, and

findings in an inspection.

(9) Standards of Practice - §535.227 of this title (relating to Standards of Practice: General Provisions), §535.228 of this title (relating to Standards of Practice: Inspection Guidelines for Structural Systems, §535.229 of this title (relating to Standards of Practice: Inspection Guidelines for Mechanical Systems: Appliances, Cooling Systems, Heating Systems, Ducts, Vents and Flues, and Plumbing Systems), §535.230 of this title (relating to Standards of Practice: Inspection Guidelines for Electrical Systems) and §535.231 of this title (relating to Standards of Practice: Optional Systems).

 

(b) Scope.

(1) The standards of practice are the minimum levels

of inspection practice required of inspectors for the

accessible parts, components, and systems typically

found in improvements to real property, excluding

detached structures, decks, docks and fences. The

inspector may provide a higher level of inspection

performance than required by the standards of practice

and may inspect parts, components, and systems in

addition to those described by the standards of practice.

 

(2) The inspector shall:

 

(A) inspect items, parts, systems, components and conditions which are present and visible at the time

of the inspection, but the inspector is not required to

determine or estimate the remaining life expectancy or

future performance of any inspected item, part, system

or component;

(B) operate mechanical and electrical equipment,

systems, and appliances during an inspection in normal

modes and operating range at the time of the inspection;

(C) report which of the parts, components, and systems present in the property have or have not been inspected;

(D) report as in need of repair inspected parts, components or systems that are not functioning or that

the standards of practice require the inspector to report

as in need of repair;

(E) address all of the parts, components, and systems contained in the standards of practice in the property being inspected.

(F) complete the standard inspection report form

under §535.223 of this title (relating to Standard Inspection Reports)if that section applies; 

(G) identify in any written report the inspector who

performed the inspection by name and license number;

(H) comply with any other law or license requirement necessary to perform inspections or services other than what is required by the standards of practice, such as an air-conditioning and refrigeration contractor license which may be required for the inspector to make a direct in-line connection to a refrigerant system, or a structural pest control license which may be required to perform a wood-destroying-insect inspection;

 

(3) In the event of a conflict between a specific provision and a general provision in the standards of practice, the specific provision controls. The standards of practice do not apply to the following:

(A) parts, components or systems other than those specifically described; 

(B) conditions other than those specifically described, such as environmental conditions, presence of toxic or hazardous wastes or substances, presence of termites or other wood-destroying insects or organisms, compliance with codes, ordinances, statutes or restrictions or the efficiency, quality, durability of any item inspected;

(C) any part, component or system the inspector excludes under the departure provision in this section; and

(D) any determination of insurability or warrantability of any part, component or system.

 

(c) Departure Provision. 

 

(1) An inspector shall exclude from the inspection any part, component or system which the inspector is not competent or qualified to inspect.

(2) An inspector may exclude any part, component or system required for inspection by the standards of practice which is inaccessible, cannot be inspected due to circumstances beyond the control of the inspector, or

the inspector’s client has agreed is not to be inspected.

(3) This departure provision does not prohibit an inspector from specializing nor require the inspector to specifically exclude other parts, components or systems not ordinarily considered a part of the inspector’s specialty. However, the inspector shall comply with the standards of practice for the items being inspected. 

(4) If an inspector excludes any part, component or system listed in the standards of practice, other than one which the client has agreed is not to be inspected, the inspector shall:

(A) advise the client at the earliest practicable time that the specific part, component or system will not be included in the inspection; and 

(B) state in any written inspection report that the excluded part, component or system was not inspected.

 

(d) Enforcement. 

Failure to comply with §535.227 of this title (relating to Standards of Practice: General

Provisions), §535.228 of this title (relating to Standards

of Practice: Inspection Guidelines for Structural

Systems, §535.229 of this title (relating to Standards of

Practice: Inspection Guidelines for Mechanical Systems:

Appliances, Cooling Systems, Heating Systems, Ducts,

Vents and Flues, and Plumbing Systems), §535.230 of

this title (relating to Standards of Practice: Inspection

Guidelines for Electrical Systems) and §535.231 of this

title (relating to Standards of Practice: Optional Systems) is a ground for disciplinary action as prescribed by the Act, §23 (1)(7) and §535.224 of this title (relating to Proceedings before the Committee).

 

§535.228. Standards of Practice: Inspection Guidelines

for Structural Systems.

 

(a) Foundations. The inspector shall:

(1) report the type of foundation (for example, slab-on-grade or pier and beam);

(2) inspect the foundation, related structural components and/or slab surfaces; 

(3) inspect the crawl space area to determine the

general condition of foundation components and report

the method used to observe the crawl space if the

inspector did not enter the crawl space because the space

was inaccessible, hazardous conditions were present, or

access or visibility was limited;

(4) render a written opinion as to the performance

of the foundation;

(5) report general indications of foundation movement that are present and visible, such as sheetrock cracks, brick cracks, out-of-square door frames or floor slopes;

(6) report as in need of repair any post tensioned cable ends that are not protected;

(7) report as in need of repair a crawl space that does not appear to be adequately ventilated;

(8) report as in need of repair conditions or symptoms that may indicate the possibility of water penetration that are present and visible, such as improper grading around foundation walls or plumbing leaks; and

(9) report as in need of repair conditions that are present and visible and may be adversely affecting foundation performance, such as erosion or water ponding.

 

(b) Specific limitations for foundations. The inspector

is not required to enter a crawl space or any areas where

headroom is less than 18 inches and the width of the

access opening is less than two feet, or where the inspector reasonably determines conditions or materials

are hazardous to health or safety of the inspector.

 

(c) Interior walls, doors, ceilings and floors. The

inspector shall:

(1) report as in need of repair deficiencies of the surfaces of walls, ceilings and floors as related to structural performance or water penetration that are present and visible;

(2) report as in need of repair accessible doors that

do not operate properly, excluding locks and latches;

(3) report as in need of repair deficiencies in steps,

stairways, balconies and railings; 

(4) report as in need of repair spacings between

intermediate balusters, spindles, or rails for steps, stairways, balconies, and railings that permit passage of

an object greater than four inches in diameter; and

(5) report as in need of repair the absence of safety

glass in hazardous locations.

 

(d) Specific limitations for Interior walls, doors, ceilings and floors. The inspector is not required to do the following:

(1) determine the condition of floor, wall or ceiling

coverings unless such conditions affect structural performance or indicate water penetration;

(2) report obvious damage to floor, wall or ceiling

coverings;

(3) determine the condition of paints, stains and other

surface coatings; or 

(4) determine condition of cabinets.

 

(e) Exterior walls and doors, windows and door

glazing. The inspector shall:

(1) report as in need of repair present and visible deficiencies of exterior walls that are related to structural performance and water penetration;

(2) report as in need of repair deficiencies in the condition and operation of exterior doors and garage doors, including door locks and latches when present.

(3) report as in need of repair damaged glazing in windows and exterior doors;

(4) report as in need of repair any insulated windows that are obviously fogged or display other evidence of broken seals;

(5) report as in need of repair the absence of safety glass in hazardous locations;

(6) report as in need of repair missing or damaged window and door screens;

(7) report as in need of repair in homes having burglar bars the absence of functional keyless burglar bars in appropriate locations;

(8) report as in need of repair inoperable windows at burglar bar locations of sleeping rooms or egress areas and any inoperable windows at other randomly sampled accessible burglar bar locations; and 

(9) report as in need of repair spacings between intermediate balusters, spindles and rails that permit passage of an object greater than four inches in

diameter.

 

(f) Specific limitations for exterior walls and doors,

windows and door glazing. The inspector is not required

to do the following:

(1) report the condition or presence of storm windows or doors, awnings, shutters or security devices or systems;

(2) determine the condition of paints stains or other surface coatings; or

(3) determine the presence of, or extent or type of, insulation or vapor barriers in exterior walls.

 

(g) Fireplace and chimney. The inspector shall:

(1) report as in need of repair deficiencies in the visible components and structure of the chimney and fireplace;

(2) inspect the interior of the firebox and the visible

flue area, and report as in need of repair built up creosote in visible areas of the firebox and flue (the inspector is not required to determine the adequacy of the draft or perform a chimney smoke test);

(3) report as in need of repair a damper that does not

operate;

(4) report as in need of repair the absence of non-combustible hearth extension;

(5) report as in need of repair deficiencies in the lintel, hearth and material surrounding the fireplace, including clearances from combustible materials; 

(6) report as in need of repair the absence of firestopping at the attic penetration of the chimney flue, where accessible;

(7) report as in need of repair any gas log lighter valves that do not function or leak gas; 

(8) report as in need of repair any circulating fan that

does not operate, if present; 

(9) report as in need of repair deficiencies in combustion air vent, if present; and

(10) report as in need of repair deficiencies in chimney coping or crown, caps or spark arrestor (inspected from ground level at a minimum).

 

(h) Roof, roof structure and attic. The inspector shall:

(1) report the type of roof covering and report as in

need of repair:

(A) a roof covering that is not appropriate for the

slope of the roof;

(B) fasteners that are not present or that are not

appropriate, (where it can be reasonably determined);

and

(C) roof jacks, flashing and counter flashing that

are not present or not properly installed.

(2) inspect the general condition of, and report evidence of previous repairs to, flashing, skylights and other roof penetrations;

(3) report as in need of repair inadequate attic space

ventilation;

(4) report as in need of repair deficiencies in the roof covering, structure and sheathing;

(5) report any visible evidence of moisture penetration;

(6) report as in need of repair the lack of or inappropriate installation of components such as purlins, struts, collar ties or rafter ties, where necessary;

(7) report as in need of repair excessive deflections or depressions in the roof’s surface relating to the performance of the framing and the roof deck;

(8) enter and inspect attic space(s) except when inadequate access or hazardous conditions exist as

reasonably determined by the inspector and report the

method used to inspect the attic if the inspector did not

enter the attic;

(9) report the method used to inspect the roof if the

inspection is performed from other than roof level;

(10) inspect for the presence, and report the approximate depth of, insulation where visible; and 

(11) report as in need of repair deficiencies in visible installed gutter and downspout systems.

 

(i) Specific limitations for roof, roof structure and attic. The inspector is not required to do the following:

(1) determine the remaining life expectancy of the roof covering; or

(2) inspect the roof from the roof level if the inspector reasonably determines that the inspector cannot safely reach or stay on the roof, or that damage to the roof or roof covering may result from walking on the roof.

 

(j) Porches and decks. The inspector shall:

(1) report as in need of repair structural deficiencies

in porches, decks, steps, balconies and carports as to

visible footings, joists, deckings, railings and attachment

points, where applicable; and

(2) report as in need of repair (except for decks

which are not higher than 30 inches as measured from

the adjacent grade) spacings between intermediate balusters, spindles or rails that permit passage of an

object greater than four inches in diameter. 

 

(k) Specific limitations for porches and decks. The

inspector is not required to inspect detached structures or

waterfront structures and equipment, such as docks or

piers.

 

§535.229. Standards of Practice: Inspection

Guidelines for Mechanical Systems: Appliances,

Cooling Systems, Heating Systems, Ducts, Vents and

Flues, and Plumbing Systems.

 

(a) Dishwasher. The inspector shall:

(1) report as in need of repair any deficiencies in the

door gasket, control knobs and interior parts, including

the dish tray, rollers, spray arms and the soap dispenser;

(2) report as in need of repair any interior signs of rust;

(3) report as in need of repair a door spring that does

not operate properly;

(4) report as in need of repair deficiencies in the discharge hose or piping or the lack of back flow prevention;

(5) report as in need of repair units that are not securely mounted;

(6) report as in need of repair any water leaks;

(7) inspect the unit’s operation in normal mode with

the soap dispenser closed; and

(8) report as in need of repair spray arms that do

not turn, soap dispensers that do not open or drying

elements that do not operate.

(b) Food waste disposer. The inspector shall:

(1) report as in need of repair any deficiencies in the

splash guard, grinding components, wiring and exterior;

(2) report as in need of repair a unit that is not securely mounted; and

(3) inspect the operation of the unit and report as in

need of repair any unusual noise or vibration level and

any signs of water leaks.

(c) Range exhaust vent. The inspector shall:

(1) report as in need of repair any deficiencies in the filter, vent pipe, light and switches;

(2) inspect the operation of the blower and report as

in need of repair any unusual sounds or vibration levels,

or if the blower does not operate at all speeds;

(3) report as in need of repair a vent pipe that does

not terminate outside the structure when the unit is not

of recirculating type or configuration.

(4) report as in need of repair a vent pipe that is of

inadequate material; and

(5) report as in need of repair the absence of a range

exhaust vent.

(d) Electric or gas ranges. The inspector shall:

(1) report as in need of repair broken or missing

knobs, elements, drip pans or other parts, inadequate

clearance from combustible material, or the absence of

an anti-tip device;

(2) report as in need of repair signal lights and elements or burners that do not operate at low and high settings;

(3) report as in need of repair improper materials

that are used for the gas branch line and the connection

to the appliance; and

(4) report as in need of repair the absence of a gas

shut-off valve, or valve that is not properly located, is

inaccessible, or leaks.

(e) Electric or gas ovens. The inspector shall:

(1) report as in need of repair any broken or missing

knobs, handles, glass panels, door hinges, lights or light

covers or other parts, or inadequate clearance from

combustible material;

(2) report as in need of repair deficiencies in the door gasket, tightness of closure and operation of the latch;

(3) report as in need of repair an oven that is not securely mounted;

(4) report as in need of repair heating elements and thermostat sensing elements that are not properly

supported;

(5) report as in need of repair deficiencies in the operation of the heating elements or the lighting, operation and condition of the flame;

(6) report as in need of repair deficiencies in the

operation of the clock and timer, thermostat and door

springs; and

(7) report as in need of repair any inaccuracy of the

thermostat more than a 25 degree range plus or minus of

a 350 degree setting, as measured by a thermometer.

(f) Microwave oven. The inspector shall:

(1) report as in need of repair any broken or missing

knobs, handles, glass panels, or other parts, or a unit that

is not securely mounted;

(2) report as in need of repair any deficiencies in the door and seal (the inspector is not required to test for

radiation);

(3) report as in need of repair an oven that does not

operate by heating a container of water or with other test

equipment, as reasonably determined by the inspector;

and

(4) report as in need of repair a light that does not operate.

(g) Trash compactor. The inspector shall:

(1) inspect the overall condition of the unit;

(2) report as in need of repair a unit that does not operate or operates with unusual noise or vibration levels; and

(3) report as in need of repair a unit that is not securely mounted in place.

(h) Other built-in appliances. The inspector shall report as in need of repair any deficiencies in condition or operation of other built-in appliances not listed in this

section.

(i) Bathroom exhaust vents and electric heaters. The

inspector shall operate the unit, and report as in need of

repair unusual sounds, speed and vibration levels or,

when possible, vent pipes that do not terminate outside

the structure.

(j) Whole house vacuum system. The inspector shall:

(1) inspect the condition of the main unit;

(2) report as in need of repair a unit that does not operate; and

(3) inspect the system from all accessible outlets throughout the house.

(k) Water heaters. The inspector shall:

(1) report the energy source;

(2) inspect the unit and report as in need of repair fittings that leak or are corroded;

(3) report as in need of repair temperature and pressure relief valve piping that lacks gravity drainage, is improperly sized (no smaller than the outlet fittings),

has deficiencies in material, or lacks a correct termination;

(4) report as in need of repair a temperature and

pressure relief valve that does not operate when the valve is of an operable type and operation will not cause

damage to persons or property as reasonably determined

by the inspector (for example, it would be reasonable not

to operate the valve if there is improper or undetermined

termination of the drain pipe, a corroded or damaged

valve, improper installation of valve or drain pipe, the

drain pipe is of inappropriate material or there is no

water supply cut-off valve at the unit);

(5) report as in need of repair any broken or missing parts, covers or controls;

(6) report as in need of repair deficiencies in the burner, flame and burner compartment, the operation of heating elements and the condition of wiring;

(7) report as in need of repair deficiencies in materials used for the gas branch line and the connection to the appliance, the absence of a gas shut-off valve, or a valve that is not properly located, is inaccessible, or leaks;

(8) if applicable, report as in need of repair deficiencies in the vent pipe, draft diverter, draft hood and their condition, draft, proximity to combustibles and vent termination point, observing for adequate combustion and draft air;

(9) report as in need of repair the lack of a safety pan and drain (including the termination of the drain line)

when applicable;

(10) report as in need of repair an unsafe location or

installation; and

(11) inspect garage units or units which are located in rooms or enclosures opening into a garage and report

as in need of repair the following:

(A) a lack of protection for physical damage to the unit; and 

(B) burners, burner ignition devices or heating elements, switches or thermostats that are not a minimum of 18 inches above the lowest garage floor elevation.

(l) Doorbell and chimes. The inspector shall:

(1) inspect the condition of the unit and report as in

need of repair a unit that does not operate; and 

(2) report as in need of repair any deficiencies in visible and accessible parts.

(m) Attic power vents. The inspector shall:

(1) report as in need of repair deficiencies in the operation and installation of the unit, including the wiring

and mounting of the thermostat control, if so equipped

and accessible; and

(2) report as in need of repair unusual sounds or speed and vibration levels.

(n) Garage door operator. The inspector shall:

(1) report as in need of repair deficiencies in the installation, condition and operation of the garage door

operator;

(2) operate the door both manually and by an installed automatic door control;

(3) report as in need of repair a door that does not automatically reverse during closing cycle, any installed

electronic sensors that are not operable or not installed

at the proper heights above the garage floor; and

(4) report as in need of repair door locks or side

ropes that have not been removed or disabled.

(o) Hydrotherapy or whirlpool equipment. The inspector shall:

(1) report as in need of repair a unit that does not operate, leaks, or is inaccessible;

(2) report as in need of repair a unit that lacks a ground fault circuit interrupter or has an interrupter that does not operate;

(3) report as in need of repair switches that are not

in a safe location or do not operate;

(4) report evidence of leaks under the tub if the access cover is available and accessible, reporting when the cover is absent or inaccessible (the inspector is not required to determine the adequacy of self-draining

features of the circulation system); and

(5) report as in need of repair deficiencies in the ports, valves, grates and covers.

 

(p) Specific limitations for appliances. The inspector

is not required to do the following:

(1) operate or determine the condition of other auxiliary components of inspected items; or

(2) inspect self-cleaning functions.

 

(q) Cooling systems other than evaporative coolers.

The inspector shall:

(1) report the type of system and energy sources;

(2) operate the system using normal control devices except when the outdoor temperature is less than 60

degrees Fahrenheit;

(3) inspect for proper performance; such as by observing the temperature difference between the supply air and the return air or noticeable vibration of the blower fan and report as in need of repair any deficiencies;

(4) report as in need of repair the lack of, or deficiencies in drainage of, condensate drain line and secondary drain line when applicable, including pipes made of inadequate material;

(5) report as in need of repair a primary drain pipe that terminates in a sewer vent, if the termination is visible;

(6) report as in need of repair a safety pan that is not

appropriately sized for the evaporator coil or free of

water or debris;

(7) report as in need of repair a return chase and plenum that are not free of improper and hazardous

conditions, such as gas pipes, sewer vents, refrigerant

piping or electrical wiring.

(8) report as in need of repair the lack of insulation

on refrigerant pipes and the primary condensate drain

pipe;

(9) report as in need of repair a condensing unit that

does not have adequate clearances, or air circulation, or

that has deficiencies in the condition of fins, location,

levelness and elevation above ground surfaces; and

(10) report as in need of repair conductor sizing and

over-current protective devices that are not appropriately

sized for the unit.

 

(r) Evaporative coolers. The inspector shall:

(1) operate the motor and report as one or two speed;

(2) observe the electrical pigtail connection at the

motor;

(3) inspect the power source in the unit;

(4) report as in need of repair a pump that does not

function or deficiencies in the spider tubes, tube clips and

bleeder system;

(5) report as in need of repair deficiencies in the water supply line and float bracket;

(6) report as in need of repair the absence of a minimum one-inch air gap between water discharge at float and water level;

(7) report as in need of repair deficiencies in the fan

(blower) and squirrel cage or rust build-up, deterioration or corrosion;

(8) report as in need of repair deficiencies in the fan

belt and pulleys;

(9) report as in need of repair deficiencies in the housing side panels, the water trays, the exterior housing and the roof frame;

(10) report as in need of repair deficiencies in the roof jack or other mounting point and the location of the seasonal damper at the unit; and

(11) report as in need of repair deficiencies in the interior registers and the supply duct.

 

(s) Specific limitations for cooling systems. The inspector is not required to do the following:

(1) inspect for the pressure of the system coolant or

determine the presence of leaks;

(2) program digital-type thermostats or controls; or 

(3) operate setback features on thermostats or controls.

 

(t) Heating systems. The inspector shall:

(1) report the type of heating system and its energy

sources;

(2) report as in need of repair a system that does not

operate properly using normal control devices;

(3) report as in need of repair deficiencies in the

controls and accessible operating components of the

system;

(4) in gas units, inspect the burner, and report as in

need of repair deficiencies in the burner compartment,

type, condition, draft and termination of the vent pipe, or

proximity to combustibles; the lack of combustion and

draft air or inappropriate location, or the lack of forced

air in the burner compartment (full evaluation of the

integrity of a heat exchanger requires dismantling of the

furnace and is beyond the scope of a visual inspection);

(5) report as in need of repair gas units that display flame impingement, uplifting flame, improper flame color or excessive scale buildup;

(6) report as in need of repair gas units that use improper materials for the gas branch line and the connection to the appliance;

(7) report as in need of repair in gas units deficiencies in materials used for the gas branch line and the connection to the appliance, the absence of a gas

shut-off valve, or a valve that is not properly located, is

inaccessible, or leaks; and

(8) report as in need of repair elements in electric

furnaces that do not operate;

(9) report as in need of repair a return chase or plenum that are not free of improper and hazardous conditions, such as gas pipes, sewer vents, refrigerant piping or electrical wiring; and

(10) report if the inspector deemed the furnace to be inaccessible.

 

(u) Specific limitations for heating systems. The inspector is not required to do the following:

(1) inspect accessories such as humidifiers, air purifiers, motorized dampers, heat reclaimers, electronic air filters or wood-burning stoves;

(2) determine the efficiency or adequacy of a system;

(3) program digital-type thermostats or controls; or

(4) operate radiant heaters, steam heat systems or unvented gas-fired heating appliances.

 

(v) Ducts, vents (including dryer vents) and flues. The

inspector shall:

(1) report as in need of repair deficiencies such as

damaged ducting or insulation, improper material or

improper routing of ducts where visible and accessible;

(2) report as in need of repair the absence of air flow at all accessible supply registers in the habitable areas of the structure;

(3) report as in need of repair deficiencies in accessible duct fans and filters;

(4) report as in need of repair deficiencies in installation, such as gas piping, sewer vents, electrical wiring or junction boxes in the plenum, returns or chases or improper sealing, where visible;

(5) report as in need of repair deficiencies in the flue

system components;

(6) report as in need of repair a flue or vent pipe that does not properly terminate; and

(7) report as in need of repair deficiencies in materials used for the venting systems.

 

(w) Specific limitations for ducts and vents. The inspector is not required to do the following:

(1) determine the efficiency, adequacy or capacity of the systems;

(2) determine the uniformity of the supply of conditioned air to the various parts of the structure;

(3) determine the types of materials contained in insulation, wrapping of pipes, ducts, jackets, boilers and

wiring;

(4) operate venting systems unless ambient temperatures or other circumstances, in the reasonable opinion of the inspector, are conducive to safe operation without damage to the equipment; or

(5) operate a unit outside its normal operating range as reasonably determined by the inspector.

 

(x) Plumbing systems. The inspector shall:

(1) inspect and report as in need of repair deficiencies in the type and condition of all accessible and visible water supply and waste-water and vent pipes;

(2) inspect and report as in need of repair deficiencies in the operation of all fixtures and faucets where the flow end of the faucet is not connected to an appliance;

(3) report as in need of repair the lack of back-flow

devices, anti-siphon devices or systems or air gaps when

applicable;

(4) report as in need of repair incompatible materials

in connecting devices between differing metals in the

supply system, where visible;

(5) report as in need of repair deficiencies in water

supply by viewing functional flow in two fixtures operated simultaneously;

(6) report as in need of repair deficiencies in functional drainage at accessible plumbing fixtures;

(7) report as in need of repair deficiencies in installation and identification of hot and cold faucets;

(8) report as in need of repair mechanical drainstops

that are missing or do not operate if installed on sinks,

lavatories and tubs;

(9) report as in need of repair commodes that have

cracks in the ceramic material, are improperly mounted

on the floor, leak or have tank components which do not

operate;

(10) report as in need of repair accessible supply and drain pipes that leak;

(11) report as in need of repair the lack of a visible vent pipe system to the exterior of the structure or improper routing or termination of the vent system;

(12) report as in need of repair a shower enclosure

that leaks; and

(13) report as in need of repair any exterior faucet

attached or immediately adjacent to the structure that

does not operate properly.

 

(y) Specific limitations for plumbing systems. The inspector is not required to do the following:

(1) operate any main, branch or shut-off valves;

(2) inspect any system that has been shut down or

otherwise secured;

(3) inspect any components that are not visible or accessible;

(4) inspect any exterior plumbing components such

as water mains, private sewer systems, water wells,

sprinkler systems or swimming pools;

(5) inspect fire sprinkler systems;

(6) inspect or operate drain pumps or waste ejector

pumps;

(7) inspect the quality or the volume of well water;

(8) determine the potability of any water supply;

(9) inspect water-conditioning equipment, such as softeners or filter systems; 

(10) inspect solar water heating systems;

(11) determine the effectiveness of anti-siphon devices on appropriate fixtures or systems;

(12) operate free-standing appliances;

(13) inspect private water supply systems, swimming pools, or pressure tanks;

(14) inspect the gas supply system for leaks; or

(15) inspect for sewer clean-outs.

 

§535.230. Standards of Practice: Inspection

Guidelines for Electrical Systems.

 

(a) Service entrance and panels. The inspector shall:

(1) inspect service entrance cables and report as in

need of repair deficiencies in the integrity of insulation,

drip loop, separation of conductors at weatherheads and

clearances;

(2) report as in need of repair a drop, weatherhead

or mast that is not securely fastened;

(3) report as in need of repair the lack of a grounding

electrode conductor in the service where visible, or the

lack of secure connection to the grounding electrode or

grounding system;

(4) report as in need of repair accessible main or subpanels that are not secured to the structure or appropriate for their location (weather-tight if exposed to weather, appropriate clearances and accessibility), do not have inside covers (dead fronts) in place, do not have conductors protected from the edges of metal panel

boxes, do not have trip ties installed on labeled 240 volt circuits, do not have proper fasteners or do not have

knockouts filled ;

(5) inspect and report as in need of repair deficiencies in the type and condition of the wiring in the panels, in the compatibility of overcurrent protectors for the size of conductor being used and in sizing of listed equipment of overcurrent protection and conductors, when power requirements for listed equipment are readily available and breakers are labeled;

(6) report as in need of repair a panel that is installed in a hazardous location, such as a clothes closet;

(7) report as in need of repair the absence of appropriate connections, such as copper/aluminum approved devices, pig-tailed connections or crimp connections; and the absence of anti-oxidants on aluminum conductor terminations; and 

(8) report as in need of repair the lack of main disconnect(s).

 

(b) Specific limitations for service entrance and panels. The inspector is not required to do the following:

(1) determine service capacity amperage or voltage

or the capacity of the electrical system relative to

present or future use;

(2) determine the insurability of the property;

(3) conduct voltage drop calculations; or 

(4) determine the accuracy of breaker labeling.

 

(c) Branch circuits, connected devices and fixtures.

The inspector shall:

(1) report the type of branch circuit wiring;

(2) inspect all accessible receptacles and report as in need of repair a receptacle in which:

(A) power is not present;

(B) polarity is incorrect;

(C) the unit is not grounded, if applicable;

(D) there is evidence of arcing or excessive heat;

(E) the unit is not secured to the wall;

(F) the cover is not in place; or

(G) ground fault circuit interrupter devices are not properly installed as set forth by the current edition of

the National Electric Code, publication 70A of the

National Fire Protection Association, or do not operate

properly as shown by use of a separate testing device;

(3) operate all accessible wall and appliance switches and report as in need of repair a switch that:

(A) does not operate or is damaged;

(B) displays evidence of arcing or excessive heat; or

(C) is not fastened securely with cover in place.

(4) inspect installed fixtures including lighting devices and ceiling fans;

(5) report as in need of repair an inoperable or missing fixture;

(6) report as in need of repair deficiencies in exposed wiring, wiring terminations, junctions and junction boxes;

(7) report as in need of repair deficiencies or absences of conduit in appropriate locations or conduit that is not terminated securely;

(8) report as in need of repair appliances and electrical gutters that do not have proper bonding;

(9) report as in need of repair subpanels that are not

properly bonded and grounded;

(10) report as in need of repair the lack of disconnects in appropriate locations;

(11) inspect (if branch circuit aluminum wiring is

discovered in the main or subpanels) a random sampling of accessible receptacles and switches and report as in

need of repair the absence of appropriate connections,

such as copper/aluminum approved devices, pig-tailed

connections or crimp connections;

(12) report as in need of repair the improper use of

extension cords; and

(13) report as in need of repair the absence of, or

deficiencies in, the installation and operation of smoke

or fire detectors not connected to a central alarm system.

 

§535.231. Standards of Practice: Optional Systems.

 

(a) Scope. This section covers other systems and

attachments that an inspector may inspect. The

inspector may need special knowledge or tools to

perform these inspections. It is the responsibility of the

inspector to be properly informed and know current and

safe procedures for inspecting the items described in this

section. The inspector shall determine and provide a

report of the condition of the equipment, systems, parts

or components by visual observation and operation in

normal modes and operating range noted at the date and

time of the inspection. If an inspector agrees to inspect

a component described in this section, §535.227 of this

title (relating to Standards of Inspection: General Provisions) applies to the inspection.

(b) Inspection guidelines for gas lines. The inspector

shall:

(1) inspect and report as in need of repair deficiencies in the condition and type of all accessible and visible gas piping; and

(2) test gas lines by using a local or an industry-accepted procedure.

(c) Specific limitations for gas lines. The inspector is

not required to inspect sacrificial anode bonding or for its

existence.

(d) Inspection guidelines for outbuildings. The inspector shall:

(1) inspect the building and report as in need of repair water penetration or deficiencies in structural performance; and

(2) report as in need of repair deficiencies in electrical, plumbing, heating, ventilation or air-conditioning

systems that the standards of practice would require the inspector to report for the principal structure.

(e) Inspection guidelines for outdoor cooking equipment. The inspector shall:

(1) report the energy source and operate the unit;

(2) report as in need of repair deficiencies in operation, control knobs, handles, burner bars, grills, box, rotisserie (if present) and heat diffusion material;

(3) report as in need of repair a unit or pedestal that

is not stable;

(4) report as in need of repair gas units that use improper materials for the gas branch line and the connection to the appliance; and

(5) report as in need of repair a gas unit that has no shut-off valve, an inaccessible valve or a valve that leaks;

(f) Inspection guidelines for lawn and garden sprinkler

system. The inspector shall:

(1) operate all zones or stations on the system manually;

(2) report as in need of repair deficiencies in water

flow or pressure at the circuit heads;

(3) report as in need of repair surface water leaks, the absence or improper installation of anti-siphon valves and backflow preventers or the absence of shut-off valves;

(4) inspect and report as in need of repair deficiencies in the condition and mounting of the control box and visible wiring; and

(5) report as in need of repair deficiencies in the operation of each zone and associated valves, spray head

patterns and areas of non-coverage within the zone.

(g) Specific limitations for lawn and garden sprinkler system. The inspector is not required to inspect the automatic function of the timer or control box, the rain

sensor or the effectiveness and sizing of anti-siphon

valves or backflow preventers.

(h) Inspection guidelines for private water wells. The

inspector shall:

(1) operate at least two fixtures simultaneously;

(2) report the type of pump and type of storage equipment;

(3) report as in need of repair deficiencies in water

pressure and flow and operation of pressure switches;

(4) inspect and report as in need of repair deficiencies in the condition of visible and accessible equipment and components;

(5) r